wiring a subpanel wire size

Wiring a Subpanel Wire Size: What Size Wire Do You Need?

By Olivia Wilson
AD

Running power to a detached garage, a workshop, or a finished basement almost always leads to the same question: what size wire do I need to feed a subpanel? The answer is never a single number you can memorize. It depends on the amp rating of the panel, the distance from the main service, the conductor material you choose, and the temperature rating printed on the insulation. Miss any one of those variables and you end up with nuisance trips, overheated terminations, or an inspection that fails before you ever energize the circuit.

This guide covers the practical side of sizing a subpanel feeder. You will see how to establish the real load, how to read an ampacity table without guessing, when to bump up a size for voltage drop, and what the code requires for grounding and neutral separation. Whether you are pulling 6 AWG copper through conduit to a 60-amp panel in a shed or running 4/0 aluminum to a 200-amp shop panel, the underlying logic stays the same.

Start With the Load, Not the Breaker

The most common mistake DIYers make is buying wire based on the size of the subpanel enclosure. A 100-amp panel does not automatically require a 100-amp feeder. The panel is just a box with bus bars and breaker spaces, and its rating is a maximum, not a target. What actually matters is the calculated load the subpanel will carry and the size of the breaker protecting the feeder.

AD
100 Amp Sub Panel Wiring Diagram [GUIDE AND EXPLANATION]
100 Amp Sub Panel Wiring Diagram [GUIDE AND EXPLANATION]
How to Determine the Right Size Capacity of a Subpanel?
How to Determine the Right Size Capacity of a Subpanel?
Wire size for 100 amp basement sub-panel
Wire size for 100 amp basement sub-panel

The feeder breaker at the main service is what dictates the minimum conductor ampacity. If you install a 90-amp breaker, the wire must be rated for at least 90 amps after all adjustment and correction factors are applied. The only exception is the next-size-up rule, which allows a breaker slightly larger than the wire's ampacity in narrow circumstances where the load itself does not exceed the wire rating.

Calculating the Actual Demand Load

Add up what will realistically run at the same time. A 240-volt welder drawing 30 amps, a dust collector at 12 amps, lights, and a few receptacles do not all peak simultaneously, but the calculation has to account for the ones that do. For a dwelling subpanel, you generally follow the standard method in Article 220: general lighting at 3 volt-amps per square foot, small appliance and laundry circuits, then apply demand factors to the total.

Wiring a Subpanel - Fine Homebuilding
Wiring a Subpanel - Fine Homebuilding
an electrical panel with multiple wires attached to it
an electrical panel with multiple wires attached to it
How to Wire a Subpanel? Main Lug Installation for 120V/240V
How to Wire a Subpanel? Main Lug Installation for 120V/240V

For a workshop or garage, a practical approach is to list each piece of equipment with its nameplate amps, identify the two or three largest that might run together, and add 25 percent to motor loads. If the sum lands at 68 amps, you size the feeder for the next standard breaker above it, which is 70 amps, and then choose wire that carries 70 amps or more.

The 125% Rule for Continuous Loads

Any load expected to run for three hours or more is considered continuous, and the conductors and overcurrent device must be sized at 125 percent of that load. Electric vehicle chargers are the classic example. A 40-amp EV charger is treated as a 50-amp continuous load, which means the circuit needs conductors rated for 50 amps and a 50-amp breaker even though the charger itself only pulls 40.

AD

This rule catches people who size wire exactly to the nameplate rating. A 48-amp charger multiplied by 1.25 comes out to 60 amps, so you need 6 AWG copper at the 75°C column, not 8 AWG. Apply the same math to any heater, kiln, or compressor that runs without cycling off for hours at a time.

What Size Wire Should I Use for a 50 Amp Sub Panel?
What Size Wire Should I Use for a 50 Amp Sub Panel?
What Size Wire Do I Need for a 60 Amp Sub Panel? - The Engineering Knowledge
What Size Wire Do I Need for a 60 Amp Sub Panel? - The Engineering Knowledge
the instructions for how to wire an electrical device
the instructions for how to wire an electrical device
What wire type & size for sub-panel in a shed?
What wire type & size for sub-panel in a shed?
Sub Panel Wire Size Calculator – Accurate Wire Gauge & Load Sizing Tool
Sub Panel Wire Size Calculator – Accurate Wire Gauge & Load Sizing Tool
Wiring a Subpanel - Fine Homebuilding
Wiring a Subpanel - Fine Homebuilding

Matching Wire Gauge to Amperage

Once you know the target ampacity, the rest is table work. The National Electrical Code ampacity tables give you the allowable current for each wire size based on insulation temperature rating. Most modern THHN, THWN-2, and XHHW conductors are rated for 90°C, but the terminals on breakers and lugs are usually only rated for 75°C, so the 75°C column is the one that governs residential and light commercial work.

The table below shows the practical pairings most electricians use for subpanel feeders. Copper and aluminum are listed separately because aluminum requires roughly two sizes larger to carry the same current.

AD
Feeder BreakerCopper (75°C)Aluminum (75°C)
60 amps6 AWG4 AWG
70 amps4 AWG3 AWG
100 amps3 AWG1 AWG
125 amps1 AWG2/0 AWG
150 amps1/0 AWG3/0 AWG
200 amps3/0 AWG250 kcmil

Copper Versus Aluminum Conductors

Aluminum feeders have a bad reputation that dates back to the 1960s and 1970s, when small-gauge aluminum branch circuit wiring caused fires from loose terminations and oxidation. Modern AA-8000 series aluminum alloy used for large feeders is a completely different product and performs reliably when installed with the correct antioxidant compound and torque specifications.

Blog - Page 32 of 190 - The Engineering Knowledge
Blog - Page 32 of 190 - The Engineering Knowledge
An Electrical Subpanel Allows Extra Circuits to Be Added
An Electrical Subpanel Allows Extra Circuits to Be Added
How to Wire 120/240V Main Panel - Breaker Box Installation
How to Wire 120/240V Main Panel - Breaker Box Installation
400 amp wire size chart for home service entry
400 amp wire size chart for home service entry

For long runs to a detached building, aluminum is often the smarter financial choice. A 150-foot run of 2/0 aluminum SER cable can cost hundreds of dollars less than the equivalent copper, and the ampacity is comparable once you account for the larger size. Copper still wins on terminations in tight spaces and on short runs where the size difference is negligible.

Voltage Drop on Long Runs

Ampacity tables tell you when wire will overheat, not when it will deliver adequate voltage. Voltage drop is a separate concern governed by performance rather than code, though the code does require conductors to be sized large enough for reasonable efficiency. The widely accepted target is no more than 3 percent drop on a feeder and 5 percent total from the service to the farthest outlet.

AD

Use the formula VD = 2 × K × I × L ÷ CM, where K is 12.9 for copper and 21.2 for aluminum, I is the load in amps, L is the one-way distance in feet, and CM is the circular mil area of the conductor. A 100-amp load at 150 feet on copper works out to about 53,750 circular mils, which is slightly more than 3 AWG. Going up one size to 2 AWG copper solves the problem and keeps the voltage steady at the far end.

Installation Details That Change the Answer

Wire sizing does not happen in a vacuum. The way you install the conductors affects how much current they can safely carry. Bundling multiple cables together, running them through a hot attic, or stuffing them into an undersized conduit all require derating factors that can push you up a wire size or two.

Ambient temperature is the most frequently overlooked factor. Ampacity tables assume a 30°C (86°F) environment. If your feeder runs through an attic that reaches 130°F, you must apply a correction factor of roughly 0.71 to the wire's rating, which means a 100-amp conductor may only be good for 71 amps.

Separating Neutral and Ground in a Subpanel

A subpanel is not a second service. It must be fed with a four-wire feeder: two ungrounded conductors, one grounded conductor, and one equipment grounding conductor. Inside the subpanel, the neutral bar must be isolated from the enclosure and the ground bar must be bonded to it. The bonding screw or strap that connects neutral to the can gets removed.

The equipment grounding conductor is sized from NEC Table 250.122, not from the ampacity table. A 100-amp feeder needs an 8 AWG copper or 6 AWG aluminum ground. A 200-amp feeder needs 6 AWG copper or 4 AWG aluminum. Running a three-wire feeder to a subpanel and relying on the neutral as a ground path is a code violation and creates a serious shock hazard.

Conduit Fill, Cable Types, and Terminations

If you are pulling individual conductors through conduit, keep total fill under 40 percent for three or more current-carrying conductors. A 1-inch Schedule 40 PVC conduit comfortably holds three 3 AWG THHN conductors plus an 8 AWG ground. Bumping to 1/0 copper or 250 kcmil aluminum usually means stepping up to 1-1/2 inch or 2 inch conduit.

Direct burial cable such as UF or mobile home feeder must be buried at the depth your local code requires, typically 18 to 24 inches, and sleeved in conduit where it emerges from the ground. SER cable is for interior use only and cannot be buried. Always verify the temperature rating of the cable jacket before applying the 75°C column, and confirm that the lugs on your breaker and panel accept the conductor material and size you plan to use.

Sizing a subpanel feeder comes down to three honest answers: how much current the load actually draws, how far the power has to travel, and how the wire will be installed. Get those numbers right, consult the ampacity table, and add a size when the run gets long. Do that and the panel in your shop or garage will run cool, pass inspection, and keep working for decades without a second thought.